SVV Upright and SVN Pendent General-Purpose Water Sprinklers
Working Pressure: 0.05–1.00 MPa Connection Thread: R1/2 Applicable Standard: GOST 15150-69
Key words:
Upright Sprinkler, Pendent Sprinkler, SVV SVN Sprinklers ,
Product Description
The SVV and SVN General-Purpose Water Sprinklers are designed to spray and distribute water across the protected area for fire suppression or fire control. They can also be used to create water curtains in automatic fire suppression systems.
Two installation configurations are available:
- SVV: Installed vertically with the deflector facing upward
- SVN: Installed vertically with the deflector facing downward
These sprinklers are suitable for libraries, archives, museums, galleries, collection storage facilities, concert halls, cinemas, retail stores, offices, hotels, hospitals, and other indoor premises. They are designed for climatic version V, placement category 3 in accordance with GOST 15150-69.
Key Advantages
- Available in custom colors
- Available with pre-applied thread sealant
- Optional weld-on coupling
- Compatible with a protective sprinkler guard
- Suitable for installation above Grilyato open-cell ceilings
Available Models
Deflector Up – SVV Upright
- CBO0-PBо(д)0,35-R1/2/P57(68, 79, 93, 141, 182).B3-«CBB-10»
- CBO0-PBо(д)0,42-R1/2/P57(68, 79, 93, 141, 182).B3-«CBB-К80»
- CBO0-PBо(д)0,47-R1/2/P57(68, 79, 93, 141, 182).B3-«CBB-12»
- CBO0-PBо(д)0,60-R1/2/P57(68, 79, 93, 141, 182).B3-«CBB-К115»
- CBO0-PBо(д)0,77-R1/2/P57(68, 79, 93, 141, 182).B3-«CBB-15»
- CBO0-PBо(д)0,84-R1/2/P57(68, 79, 93, 141, 182).B3-«CBB-К160»
Deflector Down – SVN Pendent
- CBO0-PHо(д)0,35-R1/2/P57(68, 79, 93, 141, 182).B3-«CBH-10»
- CBO0-PНо(д)0,42-R1/2/P57(68, 79, 93, 141, 182).B3-«CBН-К80»
- CBO0-PHо(д)0,47-R1/2/P57(68, 79, 93, 141, 182).B3-«CBH-12»
- CBO0-PНо(д)0,60-R1/2/P57(68, 79, 93, 141, 182).B3-«CBН-К115»
- CBO0-PHо(д)0,77-R1/2/P57(68, 79, 93, 141, 182).B3-«CBH-15»
- CBO0-PНо(д)0,84-R1/2/P57(68, 79, 93, 141, 182).B3-«CBН-К160»
Technical Specifications
| Parameter | Specification |
|---|---|
| Working Pressure Range | 0.05–1.00 MPa |
| Coverage Area | 12 m² |
| Maximum Dimensions – SVN | 59 × 28 mm |
| Maximum Dimensions – SVV | 57 × 39 mm |
| Maximum Weight | 0.07 kg |
| Connection Thread | R1/2 |
| Nominal Operating Temperatures | 57°C / 68°C / 79°C / 93°C / 141°C / 182°C |
| Climatic Version | V |
| Placement Category | 3 |
| Applicable Standard | GOST 15150-69 |
Operating Temperature and Response Time
| Nominal Operating Temperature | Maximum Response Time |
| 57°C | 300 seconds |
| 68°C | 300 seconds |
| 79°C | 330 seconds |
| 93°C | 380 seconds |
| 141°C | 600 seconds |
| 182°C | 600 seconds |
FAQ
Q1: Who are we?
A: We are a fire fighting equipment manufacturer based in Fujian, China. Since 2004, we have supplied a wide range of fire safety products for domestic and international markets, including fire sprinklers, hydrants, valves, hoses and extinguishers.
Q2: How do we ensure product quality?
A: We follow strict quality control procedures from raw material inspection to production and final shipment. Pre-production samples and final inspections can be arranged according to order requirements.
Q3: What products do we supply?
A: We supply fire sprinklers, fire extinguishers, fire hydrants, fire valves, fire hoses, hose reels, fire cabinets, foam equipment and other fire fighting accessories.
Q4: Why choose Sunroom?
A: Sunroom has over 21 years of experience in fire fighting equipment manufacturing. We offer a wide product range, support customized production, and provide certificates or technical documents according to product and project requirements.
Certificate
Production workshop and exhibition area
Related Products
Contact Us
Our address
No. 55 Baoshun Road, Successful Development Zone,Quanzhou City,Fujian Province
Tel
Product Inquiry
If you are interested in our business or would like to learn more,
please leave us a message and we will contact you as soon as possible.